And they enabled the overload bypass, so that the unit will transfer to line mode if overload occurs in battery mode. They set the 'voltage point back to battery mode' to a 'Battery Fully Charged' setting, rather than the default 54V.Ĥ. They chose to set their own Floating Charging Voltage at 56.4V, rather than the default 54V. They set the maximum charging current to 20A, even though the Vision battery specs for model 6FM100P-X say they can take 30A.Ģ. I inherited this 2 year old system as part of purchasing our off-the-grid home, and have a few questions regarding the settings, so any help will be much appreciated:ġ. I have a Mecer SOL-I-AX-3Mplus48 inverter with a set of 4 Vision 6FM100P-X AGM batteries, & 3-300watt Enersol panels.Įverything appears to be working fine, and I did a load test on the batteries and they are in good shape.